Home >> Products >> Transformer Testing Equipment >> FY Series Voltage Transformer Burden >> FY Series Voltage Transformer Burden-Four Voltage

FY Series Voltage Transformer Burden-Four Voltage

PRODUCT DESCRIPTION
Standard No.: IEC60044 - 2
Products Description Voltage Transformer Burden
Products Model FY95
Rated Voltage
(User selection)
  • 100V, 100/√3V, 100/3V

  • 110V, 110/√3V, 110/3V

  • 115V, 115/√3V, 115/3V

  • 120V, 120/√3V, 120/3V

  • Or according to user`s requirements

Power Factor: COSФ=0.8, 1.0
Rated Burden (VA)
(User selection)
  • 1.25, 2.5, 5, 10, 20, 40, 80VA (Total burden: 158.75VA)

  • 1.25, 2.5, 5, 10, 20, 40, 50, 80VA (Total burden: 208.75VA)

  • 1.25, 2.5, 5, 10, 20, 40, 50, 80, 100VA (Total burden: 308.75VA)

  • Or according to user`s requirements

Accuracy Class ±3%
Operation Range (20% - 120%).Un
Frequency 50Hz or 60Hz
Withstand Voltage 2kV / 1min
Insulation Air
Operating Condition: Temperature: 10 ℃ ~ +40 ℃
Relative Humidity (RH): up to 85% (max 90%)


Remark: The technical datas in the above table is normal value, we accepts order with special specification from users


Standard No.: ANSI / IEEE C57.13
Products Description Voltage Transformer Burden
Products Model FY95
Rated Voltage
(User selection)
  • 100V,100/√3V,100/3V

  • 110V,110/√3V,110/3V

  • 115V,115/√3V,115/3V

  • 120V,120/√3V,120/3V

  • Or according to user`s requirements

Power Factor and
Rated Burden (VA):
COSФ=0.1: 12.5VA (W)
COSФ=0.2: 35VA (M)
COSФ=0.7: 25VA (X)
COSФ=0.85: 25VA/ 75VA /100VA /100VA /100VA
Total Capacity 400VA, Included Y, Z, ZZ
Accuracy Class
Operation Range (20% - 120%). Un
Frequency 50Hz or 60Hz
Withstand Voltage 2kV / 1min
Insulation Air
Operating Condition: Temperature: 10 ℃~ + 40 ℃
Relative Humidity (RH): up to 85% (max 90%)


Remark: The technical datas in the above table is normal value, we accepts order with special specification from users